application
acrylic putty paste for fire sealing constructive openings for
- pipe penetrations
- PE/PVC ≤ Ø50mm
- aluPE-X ≤ Ø75mm
- PE-Xa ≤ Ø32(54)mm
- copper ≤ Ø54mm
- steel ≤ Ø219mm
- cast iron ≤ Ø110mm - cable penetrations
- cables + bundles ≤ Ø 121mm
- cable trays, incl. wire mesh + ladders
- only seal off; coat back is NOT required! - constructive joints ≤ 50mm
– horizontal, incl. abutting walls
– vertical - smokeseal finish of Firetect pipe collar, wrap etc.
certification
proven performances related to application
- fire resistance
- up to EI 240 acc. EN 1366-3, penetration seals
- up to EI 120 acc. EN 1366-4, linear joints
- EN 1634-3, smoke resistance
- Euroclass acc. EN 13501-1+2 - acoustic performances
- 31 dB up to 60 dB, constructive joints - environmental performances eg
- BREEAM
- Indoor Air Comfort
- French VOC + CMR
- EMICODE
- AgBB + Blue Angel
- Belgian Regulation - CE marking
- acc. EAD 350454-00-1104
- acc. EAD 350454-00-1106