fire rated hdpe pipes with Firetect Graphite

hdPE pipes in walls + floors

Fire rated Firetect solution:

  • bundled hdPE pipes up to 3x Ø 50mm
  • cable fill configuration per pipe:
    – cable Ø 22mm
    – cable YMVK Ø 13mm
  • no rock wool backing required !
  • also tested in ceilings (metal stud)
  • small joint detail: 15 x 25mm
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
    – rigid floors ≥ 150mm
    – metal stud ceilings ≥ 150mm
  • fire resistance: EI 120

 
Also view:
– other Firetect solutions within application fire rated metal pipes
– other Firetect solutions within application fire rated cables + cable bundles
– Field of Application within Firetect system: fire rated metal pipes (PDF)
 
 
 
General instructions for Graphite sealant

  • application always acc. DoP No. CPR-14/0273-graphite
  • standard application on 2 sides (walls + floors)
  • apply sealant IN penetration opening
    – joint detail: 15x25mm; avoid trapping air
    – apply smoke seal with Firetect Graphite to improve smoke control