spiralo pipes in walls with Firetect PA coating

spiral pipes in walls

Fire rated Firetect solution:

  • spiralo pipes up to Ø 125mm:
    – with fire damper (circular cartridge)
    – circular cartridge tested with + without valve (principle configuration)
  • only apply PA coating !
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
  • fire resistance: EI 120 (principle configuration)

 
Also view:
fire rated spiralo pipes, application in floors
– Field of Application within Firetect system: fire rated spiralo pipes (PDF)
 
 
 
General instructions for PA coating

  • application always acc. DoP No. CPR-14/0260-coat
  • standard application: on 2 sides (walls)
  • apply PA coating, coat length 200mm, DFT approx. 1,0mm
  • mark correct perimeters using masking tape
  • set correct perimeters using masking tape
    – apply PA coating:
    – 100mm outer perimeter on constructive element
  • apply smoke seal with Firetect Acrylic: bead 8 mm