plastic pipes with Firetect Wrap

PE/PP/PVC pipes with pipe wrap

Fire rated Firetect solution:

  • PE/PP/PVC pipes up to Ø 160mm
    – aperture oversize allowance up to 15mm
    – included pipes in PA board, also as floor penetration !
    – also tested in fire rated mortar 200x1000mm
    – aesthetic (cast-in) penetration seal
  • always the right size on the job:
    – Wrap also available as Wrap-‘n-roll (roll 18 m)
  • minimum material usage with Wrap-‘n-roll:
    – 1 layer for pipes Ø40 up to Ø 90mm in mortar
    – 2 layers for pipes Ø40 up to Ø 125mm
    – 3 layers for pipes Ø140 + Ø 160mm
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
    – rigid floors ≥ 150mm
  • fire resistance: EI 30 up to EI 180, depending on configuration + application

 
Also view:
– other Firetect solutions within application fire rated plastic pipes
– Field of Application within Firetect system: fire rated plastic pipes (PDF)
 
 
 
General instructions for Firetect Wrap

  • application always acc. DoP No. CPR-14/0251-wrap
  • standard application on 2 sides:
    – Wrap: wrap tight-fit around pipe; hold in position with tape during installation
    – Wrap-‘n-roll: cut to size; see table in TDS
    – wrap required layers tight-fit around pipe; if necessary, hold in position with tape during installation
  • slide into place, flush with constructive element, yet still visible
  • apply smoke seal with Firetect Acrylic or Firetect PA sealer on either side
TOP