bundled plastic pipes with FMU/FMI pipe collar

PE/PP/PVC pipes bundled as 1

Fire rated Firetect solution:

  • PE pipes Ø 16mm up to Ø 110mm
    – max. 3 pipes bundled in 1 penetration seal
    standard pipe collars chained to each other:
    – use FMU pipe collars ≥ Ø 140mm
    – example: for 3x Ø 110mm, 1,5 pipe collar Ø 160mm is used !
  • easy installation of FMU/FMI pipe collar:
    – limited installation height
    – fastening with screws instead of rods
  • constructive element:
    – rigid walls ≥ 100mm
    – view application in other constructive element
  • fire resistance: EI 90
  •  
    Also view:
    open U-shape installed FMU/FMI pipe collar with angled pipes
    standard configurations with FMU/FMI pipe collar
    FMU/FMI pipe collar on outer box of rockwool batt
    – other Firetect solutions within application fire rated plastic pipes
    – Field of Application within Firetect system: fire rated plastic pipes (PDF)
     
     
     
    General instructions for FMU/FMI pipe collar

    • application always acc. DoP No. CPR-14/0251-collar
    • standard installation on 2 sides (walls)
    • bend pipe collars open and chain each other to the right length (no separate clips required!)
    • bend fixing lugs outwards and fit collar around pipe onto constructive element
    • mark screw positions through the lug slots
    • fastenings: non-corrosive screws and/or fire rated strike anchors
    • apply smoke seal around pipe with Firetect Acrylic or Firetect PA sealer on either side
TOP