fire rated metal pipes with Firetect PA coating

copper + steel with coatback

Fire rated Firetect solution:

  • metal pipes up to Ø 101mm:
    – copper Ø 12mm up to Ø 54mm
    – steel Ø 12mm up to Ø 101mm
    – also bundled pipes tested
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
    – rigid floors ≥ 150mm
  • fire resistance:
    – EI 30 up to EI 180, depending on configuration + application:
    – only apply PA coating
    – or PA coating combined with Graphite; click for principle detail

 
Also view:
– other Firetect solutions within application fire rated metal pipes
– Field of Application within Firetect system: fire rated metal pipes (PDF)
 
 
 
General instructions for PA coating

  • application always acc. DoP No. CPR-14/0260-coat
  • standard application on 2 sides (walls + floors)
  • apply PA coating:
    – coat length depending on configuration (see overview)
    – DFT approx. 1,0mm
    – apply smoke seal around pipe with Firetect Acrylic or Firetect PA sealer on either side
  • apply PA coating combined with Graphite sealant:
    – apply PA coating on pipe, see previous
    – apply Graphite sealant IN penetration opening
    – joint detail depending on configuration (seee overview)
    – avoid trapping air
TOP