fire rated metal pipes with Firetect Acrylic

copper + steel with Acrylic sealant

Fire rated Firetect solution:

  • metal pipes up to Ø 60mm:
    – copper Ø 12mm up to Ø 32mm
    – steel Ø 12mm up to Ø 60mm
    – non-insulated + insulated pipes: pipe insulation Armaflex 13mm + Rockwool 25mm
  • small joint detail, in general:
    – 10 x 25mm in walls
    – min. 5mm x 25mm in floors
    – no rock wool backing necessary !
  • constructive element:
    – rigid walls ≥ 100mm
    – rigid floors ≥ 150mm
  • fire resistance: EI 60 up to EI 120

 
Also view:
– other Firetect solutions within application fire rated metal pipes
– Field of Application within Firetect system: fire rated metal pipes (PDF)
 
 
 
General instructions for Acrylic sealant

  • application always acc. DoP No. CPR-14/0273-acrylic
  • standard application on 2 sides (walls + floors)
  • joint detail depending on configuration + application; in general:
    – width for walls: min. 10mm
    – width for floors min. 5mm
    – depth: min. 25mm (walls + floors); avoid trapping air