fire resistant duct cladding

fire resistant duct cladding

  • ducts ≤ 500mm in walls:
    – with PA board 50mm
    – fastening with PA spirals for proven board-to-board connections
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
    – view application in rigid floors
  • fire resistance acc. EN 1366-3:
    – EI 60, principle configuration
    – smoke control acc. EN 1634-3
  • easy + correct installation:
    – always apply acc. DoP No. CPR-14/0260-board
    – ensure duct is correctly mounted acc. instructions by manufacturer

    – cut PA board to size:
    1 layer PA board for cladding 1500mm towards fire compartment
    – 2x PA board strips for a tight-fit positioning in opening

    – ‘butter’ all cross cut edges of PA board + opening with PA coating
    – position PA board strips tight-fit + butt joint
    – use PA spirals for board-to-board connections
    – seal off adjacent joints with 5mm Acrylic or PA sealer
    [dkpdf-button]

product development by common practice

Firetect, it's a system!

fire resistant ducts in walls
- 1 layer PA board
- proven fastening with PA spirals

INTERCHANGEABLEINTERCHANGEABLE

use Firetect Acrylic or PA sealer to seal off

EASYEASY

only 1500mm duct cladding with 1 layer

CERTIFIEDCERTIFIED

proven fire resistant perfomances related to application