fire rated cables + bundles with Firetect Acrylic

cables + bundles with acrylic sealant

Fire rated Firetect solution:

  • electric cables up to Ø 90mm:
    – single + bundled
    – wire pipes Ø 16mm with wires, tested !
    – various cable configurations: YMVK, Cu Ø 25mm etc.
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
    – rigid floors ≥ 150mm
    – also tested in PA board; click for principle detail
  • fire resistance: EI 30 up to EI 240, depending on configuration + application

 
Also view:
– other Firetect solutions within application fire rated cables + cable bundles
– Field of Application within Firetect system: fire rated cables + cable bundles (PDF)
 
 
 
General instructions for Acrylic sealant

  • application always acc. DoP No. CPR-14/0273-acrylic
  • standard application on 2 sides (walls + floors)
  • apply sealant:
    – if required, first apply rock wool backing in penetration opening
    – joint detail: bead 8mm onto constructive element or min. 5 x 10mm in constructive element, depending on configuration (see overview)
    – avoid trapping air
TOP