fire resistant cable trays in walls

fire resistant cable trays

  • cable trays ≤ 500mm in (large) openings:
    – up to 600x1200mm in walls
    – up to 600x5000mm in floors
    – in PA board: only seal off; NO coat back required
  • optimized working space:
    – minimum inner distances between different service penetrations in 1 opening
    – maximum Cu cable fill, 1 cable tray = 60% = 19356 mm2 (LARGE) + 7835 mm2 (MIXED)
  • constructive element:
    – flexible walls ≥ 100mm
    – rigid walls ≥ 100mm
    – view application in rigid floors
  • fire resistance acc. EN 1366-3:
    – EI 60 with 2x PA board 50mm in flexible + rigid walls
    – EI 30 with 1x PA board 50mm in rigid walls
  • easy installation:
    – always apply acc. DoP No. CPR-14/0260-board
    – cut PA board to size for a tight-fit positioning in opening
    – cut out service diameter for cable tray
    – ‘butter’ all cross cut edges of PA board + opening with PA coating
    – press PA board tight-fit in opening
    – seal off cables IN PA board with 5mm joint Acrylic or PA sealer
    – coat back on cables + cable trays + perimeters is not required